低温变频机组(科莱泰克)2023

发布时间:2023-11-22 | 杂志分类:其他
免费制作
更多内容

低温变频机组(科莱泰克)2023

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第1页/共24页目录1、致用户··························································································22、产品简介·······················································································33、电气控制及安装··············································································44、机组安装·······················································································125、运行调试······················································································... [收起]
[展开]
低温变频机组(科莱泰克)2023
粉丝: {{bookData.followerCount}}
文本内容
第1页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第1页/共24页目录1、致用户··························································································22、产品简介·······················································································33、电气控制及安装··············································································44、机组安装·······················································································125、运行调试·······················································································156、故障代码表及解决措施·····································································167、维护保养·······················································································208、机组参数·······················································································229、热泵基本原理·················································································24警告1. 机组拆箱后,请检查制冷系统的压力。如压力低于 0.2Mpa,不得进行后续的安装工作,请联系经销商,检查系统的气密性。

2. 开机前先核对铭牌内电源规格与实际送电必须相符,并预热 6 个小时后,才能开机。3. 主机出厂前已在本厂测试完毕,所以安全保护开关均已设定妥当,用户切勿自行调整。

4. 检修时请断开机组电源,不可带电操作,以免机组启动造成人员伤亡。5. 机组冬季停止运行时,机组绝对不能断电,防止机组冻坏。

6. 冬季长期停机时应排放干净系统里的水,以防止机组冻坏。

第2页

佛山铠耐空调设备有限公司第 2页/共 24页 建筑冷热源一体化解决专家

致 用 户

1、 欢迎购买科莱泰克泵机组产品,在安装使用本设备之前,请阅读本手册,阅读后,请妥善保管好本手册,以备以后参考。安装和维修需要熟悉国家和当地安全规范的专业人员承担。如果在安装维修及使用中未能遵守本手册所包含的说明和注意事项及安全规范,可能会导致设备的损坏或财产损失,并且有可能造成操作人员的伤害。最好的预防是正确的安装、正确的操作和经常性的维护与保养。2、 由于科莱泰克将不断改进产品质量及性能,保留未经通知更改产品型号的权力,并不因此承担任何义务。

3、 在阅读本手册中,如果您需技术咨询,请您与科莱泰克公司或当地销售商联系。注意:一旦发生器具以外的接地系统异常情况时,应立即停止使用热泵机组。并拔下其电源插头或断开与供电电路的一切连接,并与制造厂的维修人员联系处理。

第3页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第3页/共24页产品简介安全可靠

科莱泰克热泵机组是使用电力但不利用电力加热的热水装置。因为不使用电力直接加热,水电完全隔离,安全系数进一步提高。它没有电热泵机组、燃气热泵机组使用中存在的易触电、易燃、易爆、易中毒等安全问题,是当今较为安全的热水供给设备。高效省电

科莱泰克热泵机组采用热泵制热,从空气中获得大量的免费热能,因此提供相同的热水量,用电量仅仅是传统电热泵机组的四分之一左右,可为用户省下大笔的用电费用。绿色环保

科莱泰克热泵机组采用太阳能、空气热能和电能三种干净能源,没有使用油、煤、气等矿物燃料所造成的环境污染。它在工作过程中没有排放有害气体,用户即使在密闭的空间里沐浴,也不用担心人体健康方面的问题。

全天候使用

热泵机组不受阴、雨等恶劣天气的影响,一天二十四小时能全天候使用,弥补了一般太阳能受天气环境影响,不能保证一年三百六十五天随时供应热水的缺点。且安装有精确的水温控制系统,保证在沐浴过程中有恒定水温。

长久耐用

科莱泰克热泵机组使用的压缩机、四通阀等主要零配件采用世界名厂生产的优质产品,再加以合理完善的生产工艺、严格的质检手段,使机组的性能完全得到了可靠保证。且经过严谨的测试,其使用寿命长达十年以上,远高于其它类型热泵机组的使用寿命。安装简单

科莱泰克热泵机组安装简便,且不受环境限制,可安装在楼顶、阳台、车库、厨房、储物间、地下室等地方,不须专人看管,不须设置专用机房。操作简便,智能化运行安全可靠

智能化运行,可根据负荷变化自动调整投入运行的机组数量,实现最佳节能运行。完善可靠的全自动控制系统,同时机组设计配有多种保护措施,并有自动防冻、自动除霜等多种控制,使机组运行安全可靠,操作更为简单。

应用广泛

热泵机组可满足普通家庭和工厂、学校、宾馆、酒楼、医院、美容院、洗衣店、洗浴中心等单位的需求,为用户提供源源不断的生活、生产所需热水。

第4页

佛山铠耐空调设备有限公司第 4页/共 24页 建筑冷热源一体化解决专家

电 气 控 制 及 安 装

一、操作面板

名称 符号 状态 功能或含义热水符号 常亮 制热状态

化霜符号 常亮 化霜状态

压缩机符号 常亮 压缩机运行中风机符号 常亮 风机运行中

水泵符号 常亮 水泵运行中

电辅热符号 常亮 电辅热运行中(正常)电辅热符号 闪烁 电辅热运行中(速热)摄氏度符号 常亮 当前显示的是摄氏温度时间符号 常亮 显示当前的一个实时时间定时时段 1 符号 常亮 设置定时时段1 的时间定时时段 2 符号 常亮 设置定时时段2 的时间定时符号 常亮 定时开关机开启中制冷图标

制热模式图标

时钟/定时/功能显示

锁屏图标

化霜进入图标定时开标志定时关标志温度显示图标热水模式

第5页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第5页/共24页电气控制及安装名称 符号 状态 功能或含义锁键符号 常亮 当前按键已锁定二、按键功能

序号 按键名称 图标 功能描述1 开关键

开关机;

2 功能键

模式切换

3 定时键

时钟设置;定时开关机设置4 加键

水温+或翻页5 减键

水温-或翻页6 锁定键

按键锁定

7 组合键 “ ”+“ ” 强制“化霜”开启或关闭1. 线控操作

2.1 开机和关机

在主界面时,长按“开/关”键 3 秒可切换开/关机。

锁键时,长按“开/关”键 3 秒可进行解锁操作。

2.2 设定温调节:

2.2.1 开机制热时,可对进水水温进行调节,在主界面按”△”“▽”键即可调节所需制热温度。2.2.2 开机制冷时,可对进水水温进行调节,在主界面按”△”“▽”键即可调节所需制冷温度。2.3 机组状态查询

在主界面时,长按“▽”键 3 秒可进入查看温度参数。如下表

机组状态表:

查询代码 代表意义 显示范围01 进水温度 -30~99℃02 出水温度 -30~99℃

第6页

佛山铠耐空调设备有限公司第 6页/共 24页 建筑冷热源一体化解决专家

电气控制及安装查询代码 代表意义 显示范围03 环境温度 -30~99℃04 排气温度 0~125℃05 回气温度 -30~99℃06 外盘管温度 -30~99℃07 经济器进温度 -30~99℃08 经济器出温度 -30~99℃09 内盘管温度 -30~99℃10 主膨胀阀开度

11 增焓膨胀阀开度

12 压机电流

13 散热片温度

14 直流母线电压值

15 压机实际频率

16 直流风机风速

17 预留

18 故障记录 1 上电清除记录19 故障记录 2 上电清除记录20 故障记录 3 上电清除记录2.4 时钟设定:

长按【定时】键 3 秒后进入时钟闪烁状态,此时再按一下【定时】键便可进入时钟设置状态,首先是小时位闪烁,表示可以通过”△”“▽”键调整当前时间的小时值。每按1 次”△”键小时加一,每按 1 次 “▽”键小时减一。设置好小时位数值后,再按一下【定时】键;此时分钟位闪烁,表示可以通过”△”“▽”键调整当前时间的分钟值。设置好分钟位数值后,再按一下【定时】键结束。2.5 定时设定:

按一下【定时】键进入时段选择,此时显示“时段 1”,按”△”“▽”键可选择不同的时段进行设置;

再按一下【定时】键进入时段 1 设置,按”△”“▽”键可修改定时时间;其它时段设置依次类推;在定时设置界面中,长按一下“定时”键 5 秒,则取消当段定时开/关;2.6 系统参数设置

长按”△”键 3 秒可进入参数查询状态,按”△”或”▽”键查询参数,然后按“功能键”后可通过”△”或”▽”键更改参数,更改完成按“功能键”确认并退回到查看状态。

第7页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第7页/共24页电 气 控 制 及 安 装

系统参数表:

设置代码 参数名称 调整范围 初始值P01 空调回差温度 1℃~18℃ 3℃P04 制冷设定温度 7℃~30℃ 12℃P05 制热设定温度 15℃~50℃ 45℃P09 进水温度补偿 -5℃~15℃ 0℃P11 除霜周期 20MIN~90MIN 45MIN

P12 除霜进入温度 -15℃~-1℃ -3℃P13 除霜时间 5MIN~20MIN 10MIN

P14 除霜退出温度 1℃~40℃ 20℃P15 除霜的环境与盘管温差 0℃~15℃ 8℃P16 除霜的环境温度 0℃~20℃ 17℃P17 主膨胀阀动作周期 20S~90S 20S

P18 主膨胀阀制热目标过热度 -5℃~10℃ -2℃P19 主膨胀阀调节的排气温度 70℃~125℃ 95℃P20 除霜膨胀阀开度 20~450 400

P21 主膨胀阀最小开度 50~150 50

P22 主膨胀阀模式选择 0-自动/1-手动 0

P23 主膨胀阀的手动步数 20~450 350

P24 制冷目标过热度 -5℃~10℃ -1℃P25 辅膨胀阀的手动步数 20~450 350

P26 增焓电磁阀开启环境温度 11℃~45℃ 23℃P28 恒温水泵模式:1-不停/0-停 0~1 0

P29 辅膨胀阀排气比例系数 1~6 2

P30 辅膨胀阀排气微分系数 0~180 1

P31 辅膨胀阀过热度比例系数 1~6 2

P32 辅膨胀阀过热度微分系数 0~180 1

P33 辅膨胀阀调节周期 10~20 15

P34 辅膨胀阀目标排气温度 90~120 95

P35 关闭辅膨胀阀排气温度 40~70 60

P36 辅膨胀阀目标过热度 -10~10 4

P37 辅膨胀阀模式选择 0-自动/1-手动 0

P38 主膨胀阀过热度比例系数 1~6 5

P39 主膨胀阀过热度微分系数 1~180 1

注:参数 P29,P31 ,P38 实际使用的值是除以 10(即范围为 0.1~0.6)2.7 模式转换

在开机状态主界面时,长按“功能”键 3 秒可切换工作模式;2.8 强制除霜功能

长按“功能”+“▽”键 3 秒进入强制除霜;

第8页

佛山铠耐空调设备有限公司第 8页/共 24页 建筑冷热源一体化解决专家

电 气 控 制 及 安 装

2.9 恢复出厂参数

长按“功能”+“定时”+“△”+“▽” 键 3 秒进入恢复出厂参数。2.10 变频参数设置

长按【开关】+【定时】键 5 秒进入密码输入状态,显示“0000”,按”△”或”▽”键可输入密码,再

按【定时】键可切换密码位。输入不同密码分别进入以下几种状态:

输入 4 位密码“9615”,输入完成后按【功能】键确定则进入手动频率设置状态,直接按“△”“▽” 键调整手动频率,重复此操作或重新上电则退出手动设置频率模式。输入 4 位密码“8866”,输入完成后按【功能】键确定则进入频率查看状态,原来的“小时”显示“目标频率”,原来的“分钟”显示“运行频率”,重复此操作或重新上电则退出该状态。输入 4 位密码“4180”,输入完成后按【功能】键确定,若密码输入正确则进入变频参数设置.一、 模式运行

1. 制冷模式

进水温度≥制冷设定温度+回差温度时,开机制冷;

当参数 117 选为 0 时,进水温度≤制冷设定温度时,停止制冷;

当参数 117 选为 1 时,进水温度≤制冷设定温度时,恒温控制,直至进水温度≤制冷设定温度-2℃,停止制冷;

2. 制热模式

进水温度≤制热设定温度-回差温度时,开机制热;

当参数 117 选为 0 时,进水温度≥制热设定,停止制热;

当参数 117 选为 1 时,进水温度≥制热设定温度时,恒温控制,直至进水温度≥制热设定温度+2℃,停止制热;

3. 除霜运行

 制热进入除霜条件:

制热时,压机累计运行时间≥45MIN(参数 P11),且压机持续运行时间≥5min;外盘管温度<-3℃(参数 P12);

1 (环境温度-外盘管温度)≥5℃(参数 P15),且-7℃≤环境温度≤参数P16 并持续30秒;2 (环境温度-外盘管温度)≥5℃(参数 P15),且环境温度<-7℃并持续30 秒;同时满足以上条件时,则进入除霜;(注:①和②只需满足任一条件即可)当外盘管温度故障时,若环境温度≤20℃,则除霜改为定时除霜,除霜时间为10MIN; 启动时进入除霜条件:

当停机/待机/压机断电时间≥30min 时;

-7℃≤环境温度≤3℃,且盘管温度<参数 P12;

在满足压缩机启动条件(水温低于回差/开机启动机器,但未启动)时,以上条件满足时进入除霜运行。

 退出除霜条件:

第9页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第9页/共24页电 气 控 制 及 安 装

当外盘管温度≥20℃(参数 P14)或除霜时间达到 10MIN(参数P13)时,则系统退出除霜; 除霜动作:(除霜时不关压机,只是把频率降到最低 30Hz)

进入除霜条件满足时进行下列动作:

1) 压机降到 30HZ,15 秒之后风机关;

2) 55S 时四通阀上电;

3) 60S 时压机升到除霜频率 60HZ;

4) 水泵保持运行;

退出除霜条件满足时进行下列动作:

1) 压机降到 30HZ;

2) 55S 时四通阀失电;

3) 60S 时风机开,5 秒之后压机回到正常控制频率,恢复正常制热运行; 除霜的非正常结束:

1) 在除霜期间出现故障保护停机时,系统立即退出除霜,停止运行;2) 在除霜期间不检测低压保护;

强制除霜:在外盘管温度低于退出除霜温度时,长按 M+▽键 3 秒可进入强制除霜;二、 各种负载的控制

1. 压缩机

 压缩机根据受控温度和设定温度值来决定开/关;

 压缩机关机之后,至少要间隔 3 分钟才能开;

 首次上电无 3 分钟保护;

压机

3 分钟停机保护

关 时间2. 水泵

 开机时,水泵提前压机 30 秒运行;关机时,水泵延后压机 30 秒关闭;3. 风机

 开机时,风机提前压机 5 秒开;关机时,风机延后压机 30 秒关; 在除霜时,风机停止运行。

4. 四通阀

 当参数 P27=0 时,四通阀正向:

 正常制热、关机时,四通阀失电;

 正常制冷、除霜时,四通阀得电;

 当参数 P27=1 时,四通阀反向:

 正常制热,四通阀得电;

 正常制冷、除霜、关机时,四通阀失电;

5. 曲轴电加热

 当环境温度≤7℃且压机关闭时,曲轴电加热开启;

 当环境温度≥9℃或压机开启时,曲轴电加热关闭;

6. 增焓电磁阀

制热模式:

第10页

佛山铠耐空调设备有限公司第 10页/共 24页 建筑冷热源一体化解决专家

电 气 控 制 及 安 装

 当排气温度≥100℃,增焓阀强制开启;当排气温度≤95℃时按环境温度控制: 当环境温度≤参数 P26,增焓阀开启;当环境温度≥参数 P26+2℃,增焓阀关闭;7. 底盘电加热

制热时,环境温度≤2℃打开,环境温度≥4℃关闭。除霜时候强制打开。8. 辅助电加热

 控制逻辑如下:

 启动条件:

1) 制热模式下;

2) 环境温度<0℃ 或环境温感故障

3) 制热有需求,即进水温度≤制热设定温度-回差温度(参数P1)时;4) 水泵处于运行状态

以上条件同时满足时电辅热开启。

 关闭条件:

1) 制冷模式下;

2) 制热无需求或恒温控制时;

3) 进水温度传感器出现故障报警;

4) 环境温度>0℃

5) 水流故障

6) 水泵关闭

以上任何一条件满足时,电辅热停止

 电辅热开启,水泵提前 30s 开启;辅助电加热关闭,水泵延时30s 关闭。 除霜、强制除霜、二级防冻时,强制开启电加热;

 高压故障、低压故障、排气温感故障、排气过高保护停机时,若压机锁定不能启动时,5分钟后则启动电加热代替压机运行。三、 系统保护功能

1) 通信故障

 当主板与线控通信断开 60 秒时,则报通信故障(Er09),机组继续运行;2) 环境温度故障

 机组上电后检测;

 任意时刻检测到环境温度温感短路或断路,则判断为环境温度温感故障,系统不停机; 发生此故障时,相应防冻条件取消;

 此故障可自动恢复;

 故障时线控器报维修故障;

3) 进水温度故障

 机组上电后检测;

 任意时刻检测到进水温感短路或断路,则判断为进水温感故障,系统停机保护; 此故障可自动恢复;

 故障时线控器报维修故障;

4) 出水温度故障

 机组上电后检测;

第11页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第11页/共24页电 气 控 制 及 安 装

 任意时刻检测到出水温度温感短路或断路,则判断为出水温度温感故障,系统停机保护; 发生此故障时,相应防冻条件取消;

 此故障可自动恢复;

 故障时线控器报维修故障;

5) 外盘管温度故障

 机组上电后检测;

 任意时刻检测到外盘管温感短路或断路,则判断为外盘管温感故障,系统不停机; 发生此故障时,在制热模式下主路电子膨胀阀开至手动步数; 此故障可自动恢复,发生此故障时除霜为定时除霜;

 故障时线控器报维修故障;

6) 内盘管温度故障

 机组上电后检测;

 任意时刻检测到内盘管温感短路或断路,则判断为内盘管温感故障,系统不停机; 发生此故障时,在制冷模式下主路电子膨胀阀开至手动步数; 此故障可自动恢复;

 故障时线控器报维修故障。

7) 经济器进温度故障

 机组上电后检测;

 任意时刻检测到经济器进温感短路或断路,则判断为经济器进温感故障,系统不停机; 此故障可自动恢复;

 故障时线控器报维修故障。

8) 经济器出温度故障

 机组上电后检测;

 任意时刻检测到经济器出温感短路或断路,则判断为经济器出温感故障,系统不停机; 此故障可自动恢复;

 故障时线控器报维修故障。

9) 回气温度故障

 机组上电后检测;

 任意时刻检测到回气温感短路或断路,则判断为回气温感故障,系统不停机; 发生此故障时,主路电子膨胀阀开至手动步数;

 此故障可自动恢复;

 故障时线控器报维修故障;

10) 排气温度故障

 压机开启 5 分钟后检测到排气温感短路或断路,则判断为排气温感故障,系统停机保护; 此故障可自动恢复;

 故障时线控器报维修故障;

11) 系统高压保护

第12页

佛山铠耐空调设备有限公司第 12页/共 24页 建筑冷热源一体化解决专家

电 气 控 制 及 安 装

 压机开启后,连续 5S 检测到高压开关断开,则系统停机保护; 60 分钟内发生三次此故障,则非掉电不可恢复(前两次可自动恢复); 故障时线控器报维修故障,

12) 系统低压保护

 压机开启 5 分钟后,连续 5 秒检测到低压开关断开,则系统停机保护; 60 分钟内发生三次此故障,则非掉电不可恢复(前两次可自动恢复); 故障时线控器报维修故障;

13) 排气温度过高保护

 压机开启 1 分钟后检测排气温度,当检测到排气温度≥120℃(参数P06)时,则进入排气过高保护,系统停机;

 当检测到排气温度≤95℃(参数 P07)时,则退出排气过高保护,恢复正常运行; 60 分钟内发生三次此故障,则非掉电不可恢复(前两次可自动恢复); 故障时线控器报维修故障;

14) 制冷出水过冷保护

 在制冷时,压机开启 5 分钟后检测出水温度,当连续 5 秒检测到出水温度≤5℃时,则进入制冷过冷保护,压机和风机停止运行,水泵运行根据 P28 决定; 当检测到出水温度≥7℃时,则退出制冷过冷保护,恢复正常运行; 故障时线控器报维修故障;

15) 制热出水过高保护

 在制热时,当检测到出水温度≥75℃时,则进入制热过热保护,压机和风机停止运行,水泵运行根据 P28 决定;

 当检测到出水温度≤70℃时,则退出制热过热保护,恢复正常运行; 故障时线控器报维修故障;

16) 水流保护

 水泵启动 15 秒后检测水流开关,连续 10 秒检测到此开关断开,则停机保护; 发生此故障时,如故障未恢复,则每隔 4 分钟重新启动水泵运行,检测水流情况,当60分钟内自动重启水泵 5 次后水流开关仍未闭合则不再启动水泵,直到水流开关闭合后才能再次启动水泵;

 水流故障时线控器报维修故障;

17) 系统防冻

在待机或停机保护期间

 当环境温度≤5℃时,进入一级防冻保护,打开空调阀,水泵每隔10 分钟后开启30 秒,循环运行;当环境温度≥8℃时,退出一级防冻保护;

 当环境温度≤5℃,且出水温度≤2℃时,进入二级防冻保护,自动开机制热; 当环境温度≥8℃或出水温度≥15℃时,退出二级防冻保护;

 如出水温度故障时,则由进水温度代替出水温度进行防冻;

 如环境温度故障,则进入一级防冻,是否进入二级防冻看出水温度; 如环境、出水、进水温度都出现故障时,则进入一级防冻;

第13页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第13页/共24页电 气 控 制 及 安 装

 进入防冻后线控器“循环泵”和“制热”图标闪烁;

18) 直流电机保护

 选择直流风机时,若连续 20 秒检测到直流风机失速或无反馈时,报直流风机故障,停整机;显示板显示故障代码 E64;直流风机关闭 3 分钟后自动退出故障,如60 分钟内连续出现5次,非掉电不可恢复。

2.7 保护代码查询

长按 键 10s 进入查询保护代码界面:

若同时有多个保护,轮流显示

如没有保护,显示- - - -按 键,返回主界面

二、电气安装

现场需要安装连线的线路有外接电源线、控制器线、机组连接线以及客户配置水泵电源线以及控制信号线。在机组安装到位以后,即可连接电源线电器控制及安装和连接线,所有导线必须连接牢固,并且不得与任何运动部件接触。所有连接线必须采用橡胶线(要求采用YZW-300/500、IEC57 号氯丁橡胶线),所有导线必须满足本手册要求。机组要求必须有接地措施。所有的电器设备及其安装工作都必须符合国家及当地安全规范的要求,器具应按照国家布线规则进行安装。固定线路必须配有至少 3mm 触点开距的全极断开装置。序号 机型型号 线径规格(mm2) 配置空气开关(A)1 CAR-12 2*6+1*2.5 32

2 CAR-20 2*10+1*2.5 60

3 CAR-24 2*10+1*2.5 60

3 CAR-32 2*10+1*2.5 60

注:图表所列为机组进线总线线径;地线应长于其他动力线,以防地线被拉断。信号线与主电源线必须分开单独布线。

第14页

佛山铠耐空调设备有限公司第 14页/共 24页 建筑冷热源一体化解决专家

电气控制及安装A. 电路图

电路图 A

第15页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第15页/共24页电气控制及安装电路图 B

第16页

佛山铠耐空调设备有限公司第 16页/共 24页 建筑冷热源一体化解决专家

机 组 安 装

只有专业人员才能进行机组的安装与调试!一、安装准备

验收

收到货物时应对机组进行仔细检查,以确认运输过程中是否出现货物破损现象,并按照装箱单清点主机及附件,

检查

机组出厂前已充好氟利昂,安装调试前注意检查机组在运输搬运过程中制冷剂有无泄漏。搬运

搬运时应使用叉车、起重机或吊索,将机组搬运到指定地点,搬运时要采取减震措施,防止碰撞、擦坏机组外部喷涂。机组应保持垂直状态,严禁机组倾斜角度超过30°。起吊时,吊绳不得碰风机及网罩!吊装时人员不可站于机器下方!

二、机组安装

1、安装位置

机组应安装在室外,且应与邻近墙面保持适当距离,如图12 所示,以免阻止空气流通影响空调效果,同时也便于检修。由于冷水机组具有一定的振动及噪音,安装时要求牢固、可靠,底部应稍微向后倾斜,但倾斜度不大于 5°,这样有利于冷凝水的排除。本机组可安装于地面、屋顶、阳台或其它任何便于安装并可承受机组运行重量的地方。707400地面 地面400

>200

墙面

侧面图正面图图 6 机组室外安装图

第17页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第17页/共24页机组安装A、可能避免排风方向面对常年强风方向,保证排风不会回流。B、安装位置要有足够强度,机组底脚应设减振器或减振垫,减少震动传递。C、应避免安装在脏物、落叶及昆虫聚集环境处,以防堵塞换热器。D、尽可能在机组上方安装遮阳棚,保护机组。

E、换热器应定期清扫,确保换热效率。

F、机组应安装于离电源、水源较近的地方,以便于配线和补水。G、机组不可使用还含有油、盐、腐蚀性气体的环境中,这些物质会对、机组产生腐蚀,引起故障甚至缩短机组寿命。

2、机组基础

机组可直接用膨胀螺栓固定在机座上,机座安装定位孔位置见机组外形图所示,机座可用水泥预制,预留排水沟。也可用槽钢或工字钢制作托架、加防震橡胶垫,置于地面或屋顶平面。机座表面应水平

三、水系统安装

1、循环式热水机组配管示意图

单向阀

Y型过滤器压力膨胀罐3L单向阀Y型过滤器自来水补水电辅热系统

电源控

线4m

2热

线6m

2热

线

制箱

总电源线10m

2接用户电表接室内采暖供水管接室内采暖回水管旁通阀PPR-32

PPR-32

PPR-20

PPR-20地面

水流开关截止阀

截止阀

循环水泵

截止阀截止阀图7 循环式热泵机组接管示意图

注 意

第18页

佛山铠耐空调设备有限公司第 18页/共 24页 建筑冷热源一体化解决专家

机 组 安 装

注 意: A、循环水系统配管完成后,于开机前必须将水系统中空气排尽;B、水流开关安装在水平直管段,距弯头、阀门等局部阻力件5倍以上管径C、为提高制冷(制热)效果和节约能源,管道需保温严密。

D、机组接管口必须安装排水管以方便排尽机组内水,防止冻结。E、虚线框内的配件为用户自行配置。

F、在停电或者长时间不开机时,必须将冲洗阀和排水阀打开,排干净机组及管道中的水。2、设计安装

有关室内机组及管道系统的设计安装原则应由专业人士并参照有关技术规范及技术要求进行,根据合适的屋型来设计管路走向,上图只为客户安装提供一个参考。在安装过程中,要注意几点:

A、管道布置合理,如右图所

示,应采取如 A 管路走向而非 B 管路走

向, 尽量减少,弯曲、杜绝“U”形弯、“

门”形弯。避免“U”形弯、以免由此造

成排气不畅,增大水阻,形成气塞。

图 8 水管示意图B、水管安装应垂直或水平,管路及连接部位均不得有漏水现象并保温良好。应在管道的最高处设置排气阀及补水膨胀水箱(开式水箱)。

C、水平的管道走向要保持一定的坡度(3‰),以便顺利将气体排出。D、冷水系统应参考本说明书所示方法配管,并按照水暖管道标准正确施工。E、应尽可能地减小水循环系统的阻力损失。

F、水系统与本机组进出水连接口处及水系统的最低点均设置放水口,以便在长时间停止使用时,从两处放水口同时放出机组及系统内的水,防止冬季水在换热器、水泵及管道内冻结,使机组损坏。

G、在进水管中应安装水过滤器,安装时注意流向,并在水过滤器两端加装截止阀,以便拆卸清洗过滤器。

H、水系统配管完成后,应进行水压试漏并排污,确保系统内清洁,无锈渣污物,管路方可与室外主机连接,以防污物进入机组,使换热器堵塞,造成机组损坏。AB门形弯U形弯

第19页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第19页/共24页运行调试一、运行前准备工作

1. 热泵机组检查

检查机组外观及机内管路系统是否在安装、运输过程中遭到损害。检查风机扇叶是否与风扇固定板和风扇护网干涉。

检查机组压力表是否仍有压力,确认制冷剂是否泄漏。

2. 检查配电系统

检查所供电电源是否与本说明书和机组铭牌上所要求的供电电源一致。检查所有供电和控制线路是否全部连接到位,是否按接线图正确接线,接地是否可靠,所有接线端子是否全部紧固。确认相序正确。

3. 检查管路系统

检查系统管路、补水管、回水管、压力表、温度计、阀门、水位开关等设备是否安装正确。

检查系统中应该开启的阀门是否已全部开启,应该关闭的阀门是否已全部关闭。检查机组水管内是否存在空气,若有,应利用机内水管上的手动排气阀和水泵上的排气阀,将机组管路内的空气排尽。

检查系统的保温措施是否良好。确保水系统过滤器无堵塞现象,使水路畅通无阻。确认水系统已经清洗干净

二、试运行

机组运行必须由专业人员操作!

当对整个系统进行全面检查确认符合要求后,可进行整体试运转,试运转前,压缩机须预热 12 小时。可进行整体试运行。

接通电源,开启热泵,主机延时 3 分钟后自动启动。对于三相电源机组,首先检查风扇、水泵转向是否正确,如转向不对立即关闭电源,调整相序。测量压缩机运转电流,有无异常声音。

观察水温变化以及机组的压力变化有无异常。

检查机组是否符合要求,运行一段时间后,便可投入正常使用。

第20页

佛山铠耐空调设备有限公司第 20页/共 24页 建筑冷热源一体化解决专家

故 障 代 码 表

线控器故障保护代码显示表

序号 故障原因

故障

代码

进入条件 解决措施1 主板与驱动板通讯故障 Er 10 数据线及连接问题 检查数据线并连接好主板接收操作板失败 换新的控制面板2 线控器与主板通讯故障 Er 10 数据线及连接问题 检查数据线并连接好主板接收操作板失败 换新的控制面板4 回水温度传感器损坏 Er 15

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头5 出水温度传感器损坏 Er 27

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头6 制冷蒸发盘管故障传感

器故障

Er 33

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头7 压缩机回气温度传感器

故障

Er 29

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头8 室外盘管温度传感器故

Er 16

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头9 环境温度传感器损坏 Er 21

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头10 排气温度传感器损坏 Er 18

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头11 压缩机 EVI 回气传感器

故障

Er 29

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头12 内环境温度传感器故障 Er 21

电路板上感温探头未插好或松动重新插好感温探头感温探头损坏 更换相应感温探头13 压机高压故障 Er 05

膨胀阀开度太小 调大膨胀阀过热度水流量过小

检查水管路阀是否完全打开,或更改水泵,加大流量换热器结垢

机组运行一段时间后会产生结垢现象,清洗16 压机低压故障 Er 06

膨胀阀开度太小 调大热力膨胀阀开度系统有泄漏 检漏并重新加注冷媒翅片换热器积尘

机组运行一段时间后会产生积尘现象,清洗17 水流保护 Er 03

水流开关未正确接入电控箱内端子排

正确连接好水流开关的调节弹簧的预紧力调整不正确,造成虽有足够水流量但水流开关不闭合

调整水流开关水流开关安装不正确(方向错误,水流开关的阀片选择错误)重新安装水流开关

第21页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第21页/共24页故障代码表18 进出水温差过大保护 Er 15

水流量偏小 调整水流量系统有堵塞 清理水系统水泵未运行 检查水泵E20 故障会同时显示以下故障序号,如压机输出缺相显示: E20 8 。其中 1~128 号故障优先显示,在不出现 1~128 故障时才会显示 257~384 号故障,若同时出现同等优先级两

个及以上故障则显示序号累加。例如同时出现 16、32 号故障,则显示48。故障序号 名称 描述 处理意见1 IPM 过流 IPM 模块问题 更换变频模块2 压机同步异常 压机故障 更换压机4 预留 -- -- 8 压机输出缺相 压机接线断线,接触不良 检查压机输入线路16 DC 母线电压低 输入电压过低、PFC 模块故障 检查输入电压、更换模块32 DC 母线电压高 输入电压过高、PFC 模块故障 更换变频模块64 散热片温度过高 主机风机故障、风道堵塞 检查风机,风道128 散热片温度故障 扇热片传感器短路或者开路故障 更换变频模块257 通讯故障 变频模块未收到主控发来命令 检查主控和变频模块的通讯连线258 AC 输入缺相 输入缺相(三相模块有效) 检查输入线路260 AC 输入过流 输入三相不平衡(三相模块有效) 检查输入三相相电压264 AC 输入电压低 输入电压过低 检查输入电压272 高压故障 压机高压故障(预留)

288 IPM 温度过高 主机风机故障、风道堵塞 检查风机,风道320 压机峰值电流过高 压缩机的线电流过大,驱动程序和压机不匹配

更换变频模块384 PFC 模块过温 PFC 模块温度过高 检测PFC 模块

第22页

佛山铠耐空调设备有限公司第 22页/共 24页 建筑冷热源一体化解决专家

维 护 保 养

一、电气

1、本机组应配置专用电源,电源电压波动范围为-10%至+10%,应使用自动空气开关,其额定电流为机组运行电流的 1.5 倍,绝对禁止使用闸刀开关。

注意:固定线路必须配有至少 3mm 触点开距的全极断开装置2、机组应可靠接地,定期检查机组的供电电源情况。

3、主机开关切勿频繁操作,每小时不应超过四次。电控箱应防止受潮。4、经常检查机组的电源和电气系统的接线是否牢固,电气元件是否有动作异常,如有应及时维修和更换。

5、机组安装前,所需要设定的参数,均已由公司设定完毕,一般情况下,不允许用户自行修改参数,如果确实需要,请与代理商或本公司技术服务人员联系。二、机组

1、长时停机以后再次开机前,机组必须通电预热 12 小时后才能开机,短时停机后机组不要断电,给压缩机预热,防止开机损坏压缩机。机组若长期不使用,务必将机组与管路内存水排净。机组冬季停止制热运行后,机组自动执行防冻功能,所以机组绝对不能断电。2、始终保持机组周围有良好的热交换环境,热交换器应定期除尘。3、应设专人维修保养,定期检查机组运行的压力、温度情况,检查机组的管接头及检修阀头有无泄漏,并做好记录。

三、水系统

1、系统内之循环水应保证水质良好,应定期检查、清洗过滤器,以保证足够的水流量,保证机组的换热效果。

2、水系统应配用膨胀水箱(部分机组内置),循环水应保持清洁,如果当地水质不太好,应对补水进行处理,方可进入水系统中。系统内最好使用软水。3、定期检查系统补水及排气装置运行是否正常,以免影响水循环,从而影响机组的制冷、制热效果和机组的寿命。

4、若停机时间较长,应将机组管路中的水放掉,并切断电源,套好防护罩。再运行时,开机前对系统进行全面检查。

5、机组出现故障,用户无法解决时,请电告本公司在当地的特约维修部,以便及时派人维修。

第23页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第23页/共24页维护保养6、主机冷凝器清洗,本公司建议采用 50℃-60℃、浓度为 15%的热磷酸液清洗冷凝器,启动主机自带循环水泵清洗 3 小时,最后用自来水冲洗 3 遍。(管道安装时建议预留三通接口,用丝堵封住一个接口),以备清洗时接管。禁止用腐蚀性的清洗液清洗冷凝器。7、水箱需在使用一段时间后(一般为 12 个月,具体根据当地水质而定)需清除水垢。8、常检查水系统的补水、水箱的安全阀、液位控制器和排气装置工作是否正常,以免空气进入系统造成水循环量减少,从而影响机组的制热量和机组运行的可靠性。检查水泵,水路阀门是否正常工作,水管路及水管接头是否渗漏。

注意:一旦发生器具以外的接地系统异常情况时,应立即停止使用热泵机组。并拔下其电源插头或断开与供电电路的一切连接,并与制造厂的维修人员联系处理。

第24页

佛山铠耐空调设备有限公司建筑冷热源一体化解决专家 第24页/共24页热 泵 基 本 原 理

一、热泵机组的介绍

热泵作为高效集热并转移热能的装置,可以把消耗的电力变为3 倍甚至3 倍以上的热能,实现低温热能向高温热能的搬运,是当今世界最经济最节能最安全,最环保的新一代热水制造设备。二、热泵机组及工作原理

在自然界中,水总由高处流向低处,热量也总是从高温传向低温。但人们可以用水泵把水从低处提升到高处,从而实现水的由低处向高处流动,热泵同样可以把热量从低温传递到高温。所以热泵实质上是一种热量提升装置,热泵的作用是从周围环境中吸取热量,并把它传递给被加热的对象(温度较高的物体),其工作原理与制冷机相同,都是按照逆卡诺循环工作的,所不同的只是工作温度范围不一样。

如图 12 所示,低环温变频空气源热泵机组,主要有翅片式蒸发器、压缩机、水冷冷凝器和膨胀阀四部分组成,通过让工质不断完成蒸发(吸取蒸发器中的热量)→压缩→冷凝(放出热量)→节流→再蒸发的热力循环过程,从而将低温环境里的热量转移到水中,低环温变频空气源热泵机组在工作时,与普通的空调以及热泵机组一样 ,在蒸发器中吸收低温环境介质中的能量 QA:它本身消耗一部分能量,即压缩机耗电 QB:通过工质循环系统在冷凝器中时行放热QC,QC=QA+QB,因此低环温变频空气源热泵机组的效率为(QB+ QC)/ QB ,而其他加热设备的加热效率都小于 1,因此低环温变频空气源热泵机组加热效率远大于其他加热设备的效率,可以看出,采用低环温变频空气源热泵机组作为加热装置可以节省能源,同时还降低CO2等污染物的排放量,实现节能减排的效果。进水出水节流机构

水冷冷凝器压

图 12 低环温变频空气源热泵机组工作原理图

百万用户使用云展网进行简易电子书制作,只要您有文档,即可一键上传,自动生成链接和二维码(独立电子书),支持分享到微信和网站!
收藏
转发
下载
免费制作
其他案例
更多案例
免费制作
x
{{item.desc}}
下载
{{item.title}}
{{toast}}